FD-101TURF
Field Decoder interfacing
signal line and individual valve.

|

FD-102TURF
Field Decoder interfacing
signal line
and valve or one pair of valves.

|

FD-202TURF
Field Decoder interfacing
signal line
and 2 valves or 2 pair of valves.

|

FD-401TURF
Field Decoder interfacing
signal line
and up to 4 individual valves.

|

FD-601TURF
Field Decoder interfacing
signal line
and up to 6 individual valves.

|

LSP-1TURF
Line Surge
Protection

|

SD-210TURF
Sensor Decoder interfacing signal line and analog or digital decoders.

|
|
Mounting:
In valve box or direct burial
Power Draw:
- FD-101TURF: 0.5 mA (idle) 18 mA (per active solenoid)
- FD-102TURF: 0.5 mA (idle) 18 mA (per active solenoid)
- FD-202TURF: 1 mA (idle) 18 mA (per active solenoid)
- FD-401TURF: 1 mA (idle) 18 mA (per active solenoid)
- FD-601TURF: 1 mA (idle) 18 mA (per active solenoid)
Dimensions:
- FD-101TURF: Length: 3.35 in. (85 mm),
Diameter: 1.77 in. (45 mm)
- FD-102TURF: Length: 3.35 in. (85 mm),
Diameter: 1.77 in. (45 mm)
- FD-202TURF: Length: 3.35 in. (85 mm),
Diameter: 1.97 in. (50 mm)
- FD-401TURF: Length: 3.94 in. (100 mm),
Diameter: 2.56 in. (65 mm)
- FD-601TURF: Length: 3.94 in. (100 mm),
Diameter: 2.56 in. (65 mm)
Solenoids:
- FD-101TURF: 1 address, 1 solenoid per address
- FD-102TURF: 1 address, 2 solenoids per address
- FD-202TURF: 2 addresses, 2 solenoids per address
- FD-401TURF: 4 addresses, 1 solenoid per address
- FD-601TURF: 6 addresses, 1 solenoid per address
Wires:
- FD-101TURF: Blue to cable, white to solenoid
- FD-102TURF: Blue to cable, white to solenoid
- FD-202TURF: Blue to cable, white and brown to solenoids
- FD-401TURF: Blue to cable, color-coded to solenoids
- FD-601TURF: Blue to cable, color-coded to solenoids
Surge Protection:
Built-in (FD-401TURF & FD-601TURF only)
Output Power:
Adjustable from controller
Encapsulation:
Fully waterproof
Address:
Pre-coded from factory (i.e., no switches)
Electrical Input:
Nominal voltage: 34Vpp (24V AC) from 2-wire line
Minimum voltage: 21 Vpp (15V AC)
Standby Current:
- FD-101TURF, FD-102TURF: 0.5 mA
- FD-202TURF, FD-401TURF & FD-601TURF: 1 mA
Input Fuse (FD-401TURF & FD-601TURF only):
300-500 mA, thermal
Electrical Output:
Max. voltage: 33 Vpp
Max. load:
- FD-101TURF: 1 Rain Bird solenoid
- FD-102TURF: 2 Rain Bird solenoids (two per address)
- FD-202TURF: 4 Rain Bird Solenoids (two per address)
- FD-401TURF: 4 Rain Bird Solenoids (1 per address)
- FD-601TURF: 6 Rain Bird solenoids (1 per address)
Decoder/Solenoid Wires - Electrical Resistance:
Max. 3 ohms
Max. Distance Decoder/Solenoids:
Cable length:
14 gauge: 456 feet
Wiring:
2 x 14-gauge (1.5 mm2) solid copper,
UF insulated type
Environment:
Working range: 32° to 122° F (0° to 50° C)
Storage range: -4° to 158° F (-20 to 70° C)
Humidity: 100%
Surge Protection:
40 V, 1.5 kW transil
Note: Rain Bird recommends the use of the Rain Bird DB Series Wire Connector for all connections.
Three-year trade warranty.